Draw the per unit reactance diagram for the power systems shown below. Neglect resistance and use a base of 100MVA, 220KV in 50 ohms line. The ratings of the generator, motor and transformers are
G: 40 MVA, 25 KV, X’’ = 20%; M: 50 MVA, 11 KV, X’’ = 30%
T1:40 MVA, 33 Y / 220 Y KV, X = 15%; T2: 30 MVA, 11 Δ /220Y KV, X = 15%
Load: 11 KV, 50MW + j68 MVAR
Solution:
Base MVAb new = 100 MVA; Base KVb new = 220 KV
Transmission line j50 Ω:
Zactual = j50 Ω
Transformer T1:
KVb old = 220 KV
Generator G1:
Transformer T2:
KVb old = 220 KV (HT side voltage)
Synchronous motor:
Reactance diagram: